Enclosed Sentinel UL150 (NFPA 110 compliant alarm outputs and metering), 10 A/12 V vented lead acid output, 110/120/220/240 VAC (50 Hz/60 Hz) input.
Alternate Current (AC) Operating Voltage |
N/A 95 to 250 V |
Operating Frequency |
N/A 47 to 63 Hz |
Direct Current (DC) Nominal Voltage |
N/A 12 V |
Maximum Current Limit |
N/A 5 A10 A |
Voltage Ripple |
N/A <1 % |
Line Regulation |
N/A <2 % |
Load Regulation |
N/A <2 % |
Charge Fail, Mains Alternate Current (AC) Fail |
N/A +DC During Normal Charge 1 x Solid-State Relay Open Circuit During Fault |
High and Low Battery Voltage |
N/A 2 x Solid-State Relays Closed on Fault Dry/Volt-Free Contacts |
Maximum Current Rating at 30 Direct Current (DC) Voltage (All Relay Outputs)1 | N/A 250 mA |
Standards for Maximum Current Rating at 30 Direct Current (DC) Voltage (All Relay Outputs) |
N/A UL Class 2 |
Alarm Outputs Information |
N/A
Sentinel UL150 models include a self-diagnostic circuit for monitoring charge fail fault conditions (AC supply/fuse failure, DC fuse failure or low/no charge current), with a solid-state relay output for driving a remote alarm or fault annunciator. Enclosed NFPA models have NFPA 110 compliant alarms for AC failure, charge fail, high battery volts and low battery volts. |
Operating Temperature |
N/A -4 to 140 ºF-20 to 60 ºC |
Relative Humidity |
N/A 20 to 90 % |
Electrical Safety |
N/A 2006/95/EC |
Electromagnetic Compatibility |
N/A 2004/108/EC (EN 61000-6-2, EN 61000-6-4) |
Overall Width (W) |
N/A 6.50 in165 mm |
Overall Height (H1) |
N/A 11.81 in300 mm |
Overall Height (H2) |
N/A 3.15 in80 mm |
Overall Depth (D1) |
N/A 4.92 in125 mm |
Overall Depth (D2) |
N/A 5.12 in130 mm |
Fixing Holes (X) |
N/A 2.50 in63.5 mm |
Fixing Holes (Y) |
N/A 11.25 in285.5 mm |
Weight |
N/A 4.4 lb2.0 kg |
Features |
N/A
All models feature an intelligent, multistage charge regime. During charge recovery mode, the Sentinel gives a constant (maximum) current output. As the battery approaches peak charge, the output reverts to float charge mode, maintaining an optimum cell voltage and supplying additional standing load current up to the rated maximum. Output current is always limited to the rated maximum, even during high load (e.g., engine cranking), short-circuit or reverse polarity connection. |
AutoBoost |
N/A
AutoBoost provides a temporary increase in output voltage, equalizing the charge between cells and maximizing battery life and capacity. AutoBoost is triggered automatically when the battery falls below a preset voltage or can be initiated manually through a momentary switch input. At the end of the AutoBoost cycle, Sentinel automatically reverts to normal float charge mode, preventing battery over-charge and gassing. |
Temperature Compensation |
N/A
UL Tested (listed or recognized) to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers. |
Installation and Connection |
N/A
UL Tested (listed or recognized) to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers. |
Note |
N/A
UL Tested (listed or recognized) to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers. |