Print Back
Enclosed Sentinel 300P.
Input supply 110/120/220/240 VAC (50 Hz/60 Hz).
Output 10 A at 12/24 V.
LCD readout, control/program buttons and CAN communications.
Plus analog ammeter and voltmeter.
Unit of Measure

Specifications

Model Number

N/A ESNTL300PCLM

Outputs x3 (x4 for Non-CAN Configurations)

N/A 1 x SPCO (RL1), 1 x SPNC (RL2), 1 x SPNO (RL3), dry/volt-free contacts (common feed for RL1, RL2 & RL3)

Standard Models (Non-CAN Configurations)

N/A 1 x SPNC (RL4), dry/volt-free contacts standard output functions (charge fail, AC fail, low battery volts, high battery volts) are NFPA 110 compliant.

Inputs x2

N/A Closed to negative DC to activate, configurable function

Industry Standards

N/A CE cULus NFPA 110

Electrical Connections

N/A
Electrical Connections for Sentinel 300P Programmable Switch Mode Battery Chargers

Power Supply

Alternate Current (AC) Operating Voltage

N/A 95 to 250 V

Operating Frequency

N/A 47 to 63 Hz

Direct Current (DC) Charge Output

Direct Current (DC) Nominal Voltage1 N/A 12 V24 V

Maximum Current Limit

N/A 10 A

Voltage Ripple

N/A <1 %

Line Regulation

N/A <2 %

Load Regulation

N/A <2 %

Rating (All Relays)

Maximum Current Rating at 30 Direct Current (DC) Voltage2 N/A 1 A

Standards for Maximum Current Rating at 30 Direct Current (DC) Voltage

N/A UL Class 2

Physical

Operating Temperature

N/A -40 to 60 ºC-40 to 140 ºF

Display Viewability (Liquid Crystal Display (LCD) Models)

N/A 0 to 50 ºC32 to 122 ºF

Relative Humidity

N/A 20 to 90 %

Electrical Safety

N/A 2006/95/EC

Electromagnetic Compatibility

N/A 2004/108/EC EN 55022 Class B (EN 61000-6-1, EN 61000-6-3)

UL Approvals

N/A BBGQ: UL1236, CSA22.2 no. 107.2 BBHH: UL1236 SE

Dimensions

Overall Width (W)

N/A 6.50 in165 mm

Overall Height (H1)

N/A 11.81 in300 mm

Overall Height (H2)

N/A 3.15 in80 mm

Overall Depth (D1)

N/A 4.92 in125 mm

Overall Depth (D2)

N/A 5.12 in130 mm

Fixing Holes (X)

N/A 2.50 in63.5 mm

Fixing Holes (Y)

N/A 11.25 in285.5 mm

Weight

N/A 4.4 to 4.6 lb2.0 to 2.1 kg

Standard Output Calibration

Output Calibration Information

N/A Battery type is selected by circuit board DIP switches or SNTL300P-PCSUITE configuration software.

Calibration figures at 20 ºC. If temperature compensation is enabled, and remote SNTL-RTC temperaturesensor connected, output voltage automatically varies by 3 mV per cell per 1 ºC deviation from 20 ºC, within the range -10 to +50 ºC. Increasing temperatures give decreasing outputs; decreasing temperatures give increasing outputs.

Output Calibration Specification Table

N/A
Output Calibration Specification Table for Sentinel 300P Programmable Switch Mode Battery Chargers

AutoBoost

AutoBoost

N/A Triggered automatically on low charge levels, or manually by remote switch, AutoBoost temporarily increases the charge voltage before returning to float mode. Equalizing battery cell charge without overcharge and gassing, AutoBoost maximizes cell capacity and life.

Temperature Compensation

Temperature Compensation

N/A Ensures batteries are charged at the optimal voltage, which varies significantly with ambient temperature. Sentinel can measure temperature with a battery-mounted sensor and adjusts output voltage to prevent under or over charging.

Flexible Configuration

Flexible Configuration

N/A Microprocessor programmability for automatic or manual configuration of charge output voltages (12 or 24 V nominal), cell types/numbers and application - all in one standard model. Programming is by circuit board links or PC - based software configuration and monitoring tool.

Inputs and Outputs

Inputs and Outputs

N/A For remote charger control, and signaling of charge fail, high/low battery volts and mains fail faults. Standard output functions are NFPA 110 compliant. Non-standard input/output functions available to special order.

Display, Instrumentation and Communication

Display, Instrumentation and Communication

N/A Options for backlit LCD readout, analogue metering and CAN 2.0B/SAE J1939 data communication; all models include RS485 communication for configuration and control.

The Sentinel 300P is available either as an open-frame, UL-recognized module for mounting in existing control panels, or as a UL-listed, wall-mounted stainless steel enclosure with LCD and analogue metering options. Electrical connection is by screw terminal blocks. On enclosed models, wiring harness access is by knock-out cable gland holes in the case side.

Note

Note

N/A Tested and approved by UL to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers.

In order to consistently bring you the highest quality, full-featured products, we reserve the right to change our specifications and designs at any time. Murphy products and the Murphy logo are registered and/or common law trademarks of Enovation Controls, LLC. This document, including textual matter and illustrations, is copyright protected by Enovation Controls, LLC, with all rights reserved. (c) 2015 Enovation Controls, LLC. A copy of the warranty may be viewed or printed.

Dimensions for reference only. Use actual product for mounting template. For safe heat dissipation, mount product in orientation shown, with minimum air gap clearance of 1.5 in./40 mm above/below and 1.0 in./25 mm at each side.
  • 1 Programmable
  • 2 Resistive load