Alternate Current (AC) Operating Voltage |
N/A 95 to 265 V |
Operating Frequency |
N/A 47 to 63 Hz |
Direct Current (DC) Nominal Voltage |
N/A 24 V |
Maximum Current Limit |
N/A 5 A |
Voltage Ripple |
N/A <1 % |
Line Regulation |
N/A <2 % |
Load Regulation |
N/A <2 % |
Control Input |
N/A Close to -DC to Activate Digital (Switch) Input Programmable Function |
Alarm Output |
N/A Programmable Function Relay Switched +DC |
Maximum Current Rating at 30 Direct Current (DC) Voltage (Alarm Output) |
N/A 1 A |
Protective Cover Material |
N/A 1050 Aluminum |
Protective Cover Thickness |
N/A 1.2 mm |
Operating Temperature |
N/A -30 to 60 ºC-22 to 140 ºF |
Storage Temperature |
N/A -40 to 60 ºC-40 to 140 ºF |
Relative Humidity |
N/A 20 to 90 % |
Electrical Safety |
N/A 2006/95/EC (EN 60065) |
Electromagnetic Compatibility |
N/A 2004/108/EC (EN 61000-6-2, EN 61000-6-4) |
Overall Width (W) |
N/A 4.28 in108.6 mm |
Overall Height (H) |
N/A 5.31 in135 mm |
Overall Depth (D) |
N/A 2.17 in55 mm |
Fixing Holes (X) |
N/A 3.90 in99 mm |
Fixing Holes Diameter (F) |
N/A 0.22 in5.65 mm |
Weight |
N/A 1.65 lb0.75 kg |
Features |
N/A
|
AutoBoost |
N/A The optimum charge voltage for lead acid and NiCd batteries varies with ambient temperature. Sentinel can be configured to sense battery temperature from a remote sensor and automatically compensate the output charge voltage. |
Alarm Output and Control Input ('A' Option) |
N/A The optimum charge voltage for lead acid and NiCd batteries varies with ambient temperature. Sentinel can be configured to sense battery temperature from a remote sensor and automatically compensate the output charge voltage. |
Temperature Compensation |
N/A The optimum charge voltage for lead acid and NiCd batteries varies with ambient temperature. Sentinel can be configured to sense battery temperature from a remote sensor and automatically compensate the output charge voltage. |
Versatile |
N/A The Sentinel 150P uses an open circuit board construction with an aluminum protective cover, for surface mounting in an existing control panel. Electrical connection is by quick-connect, two-part type terminal blocks. |
Installation and Connection |
N/A
Stock Code - 42.70.3619 Description - RTC sensor for remote temperature compensation feature, complete with 3 m/9.8 ft lead assembly. Non-standard lengths available to special order. Stock Code - 42.70.3825 Description - SNTL150P-PCCONN programming kit. Includes SNTL150P-PCSUITE software tool (PC compatible), USB-TTL interface and power/data connection leads. |
Accessories |
N/A
Stock Code - 42.70.3619 Description - RTC sensor for remote temperature compensation feature, complete with 3 m/9.8 ft lead assembly. Non-standard lengths available to special order. Stock Code - 42.70.3825 Description - SNTL150P-PCCONN programming kit. Includes SNTL150P-PCSUITE software tool (PC compatible), USB-TTL interface and power/data connection leads. |
Warranty |
N/A A two year limited warranty on materials and workmanship is given with this product, details available on request. |
Note |
N/A
All part numbers are supplied with output calibrated for vented lead-acid cells. Output calibration can be optimized for different battery types by using the SNTL150P-PCSUITE software tool. Dimensions for reference only. Use actual product for mounting template. For safe heat dissipation, mount product in orientation shown, with minimum air-gap clearance of 40 mm/1.5 in. above/below and 25 mm/1.0 in. at each side. |