Enclosed Sentinel UL150, 10 A/12 V vented lead acid output, 110/120/220/240 VAC (50 Hz/60 Hz) input.

Unit of Measure

Specifications

Model Number

N/A ESNTLUL1501210CDLA

UL Approvals

N/A BBGQ: UL1236, CSA22.2 no. 107.2

Industry Standards

N/A CE CSA22.2 No. 107.2 cULus UL Tested UL1236

Electrical Connections

N/A
Electrical Connections for Sentinel 150 Automatic Battery Chargers

Power Supply

Alternate Current (AC) Operating Voltage

N/A 95 to 250 V

Operating Frequency

N/A 47 to 63 Hz

Direct Current (DC) Charge Output

Direct Current (DC) Nominal Voltage

N/A 12 V

Maximum Current Limit

N/A 5 A10 A

Voltage Ripple

N/A <1 %

Line Regulation

N/A <2 %

Load Regulation

N/A <2 %

Alarm Outputs

Charge Fail, Mains Alternate Current (AC) Fail

N/A +DC During Normal Charge 1 x Solid-State Relay Open Circuit During Fault
Maximum Current Rating at 30 Direct Current (DC) Voltage (All Relay Outputs)1 N/A 250 mA

Standards for Maximum Current Rating at 30 Direct Current (DC) Voltage (All Relay Outputs)

N/A UL Class 2

Alarm Outputs Information

N/A

Sentinel UL150 models include a self-diagnostic circuit for monitoring charge fail fault conditions (AC supply/fuse failure, DC fuse failure or low/no charge current), with a solid-state relay output for driving a remote alarm or fault annunciator. Enclosed NFPA models have NFPA 110 compliant alarms for AC failure, charge fail, high battery volts and low battery volts.

Physical

Operating Temperature

N/A -4 to 140 ºF-20 to 60 ºC

Relative Humidity

N/A 20 to 90 %

Electrical Safety

N/A 2006/95/EC

Electromagnetic Compatibility

N/A 2004/108/EC (EN 61000-6-2, EN 61000-6-4)

Dimensions

Overall Width (W)

N/A 4.72 in120 mm

Overall Height (H1)

N/A 10.51 in267 mm

Overall Height (H2)

N/A 2.76 in70 mm

Overall Depth (D1)

N/A 3.74 in95 mm

Overall Depth (D2)

N/A 5.12 in130 mm

Fixing Holes (X)

N/A 2.50 in63.5 mm

Fixing Holes (Y)

N/A 10.04 in255 mm

Weight

N/A 2.8 lb1.25 kg

Standard Output Calibration

Output Calibration Information

N/A

Calibration figures shown are at 20 ºC. If temperature compensation is enabled and remote SNTL-RTC temperature sensor is connected, output voltage automatically varies by 3 mV per cell per 1 ºC deviation from 20 ºC, within the range -10 to 50 ºC. Increasing temperatures give decreasing outputs; decreasing temperatures give increasing outputs.

Output Calibration Specification Table

N/A
Output Calibration Specification Table for Sentinel 150 Automatic Battery Chargers

Features

Features

N/A

AutoBoost provides a temporary increase in output voltage, equalizing the charge between cells and maximizing battery life and capacity. AutoBoost is triggered automatically when the battery falls below a preset voltage or can be initiated manually through a momentary switch input. At the end of the AutoBoost cycle, Sentinel automatically reverts to normal float charge mode, preventing battery over-charge and gassing.

AutoBoost

AutoBoost

N/A

UL-recognized SNTLUL150 model uses an open frame circuit board and base/heatsink with protected cover, for surface or DIN rail mounting in an existing control panel. UL-listed ESNTLUL150 models use a stainless steel, wall-mounted case.

Electrical connection is by screw terminal blocks. Connection and cable access on ESNTL models is by a hinged front plate and knock-out sections in the enclosure side.

Temperature Compensation

Temperature Compensation

N/A

UL-recognized SNTLUL150 model uses an open frame circuit board and base/heatsink with protected cover, for surface or DIN rail mounting in an existing control panel. UL-listed ESNTLUL150 models use a stainless steel, wall-mounted case.

Electrical connection is by screw terminal blocks. Connection and cable access on ESNTL models is by a hinged front plate and knock-out sections in the enclosure side.

Installation and Connection

Installation and Connection

N/A

UL-recognized SNTLUL150 model uses an open frame circuit board and base/heatsink with protected cover, for surface or DIN rail mounting in an existing control panel. UL-listed ESNTLUL150 models use a stainless steel, wall-mounted case.

Electrical connection is by screw terminal blocks. Connection and cable access on ESNTL models is by a hinged front plate and knock-out sections in the enclosure side.

Note

Note

N/A

UL Tested (listed or recognized) to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers.

Dimensions for reference only. Use actual product for mounting template. For safe heat dissipation, mount product in orientation shown, with minimum air-gap clearance of 40 mm/1.5 in. above/below and 25 mm/1.0 in. at each side.

In order to consistently bring you the highest quality, full-featured products, we reserve the right to change our specifications and designs at any time. Murphy products and the Murphy logo are registered and/or common law trademarks of Enovation Controls, LLC. This document, including textual matter and illustrations, is copyright protected by Enovation Controls, LLC, with all rights reserved. (c) 2015 Enovation Controls, LLC. A copy of the warranty may be viewed or printed.

  • 1 Resistive load