As 42.70.3811, plus alarm output and control input (programmable functions).
Power Supply
Alternate Current (AC) Operating Voltage |
N/A 95 to 265 V |
Operating Frequency |
N/A 47 to 63 Hz |
Direct Current (DC) Charge Output
Direct Current (DC) Nominal Voltage |
N/A 24 V |
Maximum Current Limit |
N/A 5 A |
Voltage Ripple |
N/A <1 % |
Line Regulation |
N/A <2 % |
Load Regulation |
N/A <2 % |
Inputs and Outputs
Control Input |
N/A Close to -DC to Activate Digital (Switch) Input Programmable Function |
Alarm Output |
N/A Programmable Function Relay Switched +DC |
Maximum Current Rating at 30 Direct Current (DC) Voltage (Alarm Output) |
N/A 1 A |
Physical
Protective Cover Material |
N/A 1050 Aluminum |
Protective Cover Thickness |
N/A 1.2 mm |
Operating Temperature |
N/A -30 to 60 ºC-22 to 140 ºF |
Storage Temperature |
N/A -40 to 60 ºC-40 to 140 ºF |
Relative Humidity |
N/A 20 to 90 % |
Electrical Safety |
N/A 2006/95/EC (EN 60065) |
Electromagnetic Compatibility |
N/A 2004/108/EC (EN 61000-6-2, EN 61000-6-4) |
Dimensions
Overall Width (W) |
N/A 4.28 in108.6 mm |
Overall Height (H) |
N/A 5.31 in135 mm |
Overall Depth (D) |
N/A 2.17 in55 mm |
Fixing Holes (X) |
N/A 3.90 in99 mm |
Fixing Holes Diameter (F) |
N/A 0.22 in5.65 mm |
Weight |
N/A 1.65 lb0.75 kg |
Standard Output Calibration
Features
Features |
N/A
|
AutoBoost
AutoBoost |
N/A
A' option models include a control input and alarm output, both with configurable functions. The input can be configured for use with panel relay circuits or operator switches, giving additional control over the output, e.g. AutoBoost initiation and termination. The alarm relay output can be configured to operate during a one or more (up to 7) fault conditions: mains fail, DC connection error, battery missing, temp sensor short, low battery volts, high battery volts, charge fail. |
Alarm Output and Control Input ('A' Option)
Alarm Output and Control Input ('A' Option) |
N/A
A' option models include a control input and alarm output, both with configurable functions. The input can be configured for use with panel relay circuits or operator switches, giving additional control over the output, e.g. AutoBoost initiation and termination. The alarm relay output can be configured to operate during a one or more (up to 7) fault conditions: mains fail, DC connection error, battery missing, temp sensor short, low battery volts, high battery volts, charge fail. |
Temperature Compensation
Temperature Compensation |
N/A
The optimum charge voltage for lead acid and NiCd batteries varies with ambient temperature. Sentinel can be configured to sense battery temperature from a remote sensor and automatically compensate the output charge voltage. |
Versatile
Versatile |
N/A
Stock Code - 42.70.3619 |
Installation and Connection
Installation and Connection |
N/A
Stock Code - 42.70.3619 |
Accessories
Accessories |
N/A
Stock Code - 42.70.3619 |
Warranty
Warranty |
N/A
All part numbers are supplied with output calibrated for vented lead-acid cells. Output calibration can be optimized for different battery types by using the SNTL150P-PCSUITE software tool. |
Note
Note |
N/A
All part numbers are supplied with output calibrated for vented lead-acid cells. Output calibration can be optimized for different battery types by using the SNTL150P-PCSUITE software tool. |